尺寸 |
|
UPS
|
Batteries for 10 min back-up time
|
power
(kVA/kW)
|
width (mm)
|
weight (kg)
|
depth*
(mm)
|
width
(mm)
|
weight
(kg)
|
DELPHYS MP
|
DELPHYS MP elite
|
DELPHYS MP
|
DELPHYS MP elite
|
60/48
|
800
|
1000
|
640
|
680
|
800
|
800
|
800
|
80/64
|
800
|
1000
|
660
|
700
|
800
|
800
|
1000
|
100/80
|
800
|
1000
|
790
|
820
|
800
|
800
|
1300
|
120/96
|
800
|
1000
|
810
|
840
|
800
|
800
|
1700
|
160/128
|
800
|
1000
|
920
|
970
|
800
|
1600
|
1900
|
200/160
|
800
|
1000
|
950
|
1000
|
800
|
1600
|
2500
|
* overall depth: 845 mm |
技术数据
|
Technology |
|
On line double conversion |
VFI (Voltage Frequency Independent) |
Input |
|
Voltage (configurable) |
3-phase 380 V - 400 V - 415 V
|
Tolerance |
400 V +/- 15 %
|
Frequency (configurable) |
50 / 60 Hz
|
Tolerance |
45 to 65 Hz
|
Power Factor |
0.93 ind.
|
Current distorsion DELPHYS MX elite |
THDI < 4,5 %
|
Output |
|
Voltage (settable) |
3-phase 380 V - 400 V - 415 V
|
Tolerance (static condition) |
< 1 %
|
Tolerance (dynamic condition) on load impact 0 to 100 % |
+/- 2 %
|
Voltage distortion rate with non-linear loads |
Ph/N : < 3 %
Ph/Ph : < 2.5 %
|
Frequency |
50 / 60 Hz
|
Inverter frequency tolerance |
+/- 0.2 %
|
Admissible overload mains off |
10 mn: 125 %
1 mn: 150 %
|
Admissible crest factor without downgrading |
up to 3
|
PF admissible without downgrading |
0.1 ind to 0.9 cap.
|
Overall Efficiency |
up to 94 %*
|
In ECO-MODE configuration |
98 %
|
Environment |
|
Colour |
grey
|
Sound level at 1 m |
< 72 dBA*
|
Confity to standards
Safety
EMC
Performances
Classification as per IEC62040-3
|
IEC62040-1-2
IEC60950
IEC62040-2
IEC62040-3
ASI classe VFI - SS - 111
|
* according to power |